Motor Circuit Calculator: NEC 430 Wire, Breaker and Overload
Conductors, overload setting and breaker or fuse size for one motor under NEC Article 430.
Tool referenceDE-TOOL-8979
- Reference
- NEC 430.22, 430.32, Table 430.52
- Motors
- Single-phase and three-phase, up to 600 V
- Output
- Conductors, overload and breaker or fuse size
This motor circuit calculator sizes the branch circuit for one motor under NEC Article 430. It takes the full-load current from Table 430.248 or 430.250, sizes the conductors at 125% of it (430.22), sets the overload at 115% or 125% of the nameplate current (430.32) and gives the largest breaker or fuse allowed by Table 430.52. For a 10 hp, 460 V three-phase motor the table current is 14 A, the conductors need 17.5 A, which 14 AWG copper carries at 75 °C, and an inverse time breaker may be up to 35 A.
Motor circuit calculator (NEC 430)
Size the branch circuit for one motor under NEC Article 430: the table full-load current, the conductors at 125%, the overload setting and the largest breaker or fuse for short-circuit and ground-fault protection. Pick a quick start or enter your motor; the answer updates as you type.
The calculator needs JavaScript. The method and the NEC tables it uses are below.
Quick start Fills in the form. Change anything after.
Result
Branch circuit for a 10 hp, 460 V motor
A 10 hp, 460 V three-phase motor has a full-load current of 14 A in the NEC tables. The conductors need 17.5 A (125%), so 14 AWG copper (20 A). The inverse time breaker may be up to 35 A, and the overload is set at 17.5 A (125% of the table current; set it from the nameplate).
- Branch-circuit conductors
- 14 AWGcopper
- Full-load current, NEC table
- 14 A
- Ampacity needed (125%)
- 17.5 A
- Largest inverse time breaker
- 35 A
- Overload setting (125%)
- 17.5 A
250% of the full-load current is 35 A, a standard rating: 35 A. If the motor will not start: up to 400% of the full-load current, 56 A, so up to 50 A (430.52(C)(1)(b)).
The overload is shown from the table current. Enter the nameplate current to set it.
Screening estimate. Check the controller, overload and drive instructions, which can require other settings. Electrical design and coordination studies cover the whole system, or ask an engineer.
Full results and steps
| Full-load current, NEC table | 14 A |
|---|---|
| Conductor ampacity needed (125%) | 17.5 A |
| Conductor | 14 AWG copper, 20 A |
| Overload (125%) | 17.5 A |
| Overload, highest if the motor trips on starting (140%) | 19.6 A |
| inverse time breaker, 250% | 35 A, so 35 A |
| time-delay fuse, 175% | 24.5 A, so 25 A |
| nontime-delay fuse, 300% | 42 A, so 45 A |
| instantaneous trip breaker, 1100% | a setting of 154 A |
| Disconnect rating, at least (115%) | 16.1 A |
- Full-load current: 10 hp at 460 V, Table 430.250: 14 A. The table value, not the nameplate, sizes the conductors and the short-circuit protection (430.6(A)(1)).
- Conductors: 1.25 × 14 A = 17.5 A (430.22).
- 14 AWG copper: 25 A in the 90 °C column × 1.00 for 30 °C × 1.00 for 3 conductors = 25 A; 20 A in the 75 °C terminal column; the lower, 20 A, is at least 17.5 A.
- Overload: 125% × 14 A (table current; set it from the nameplate) = 17.5 A; up to 140%, 19.6 A, where that is not enough to start or run the motor (430.32(A)(1), 430.32(C)).
- Short-circuit and ground-fault protection, inverse time breaker: 250% × 14 A = 35 A, so up to 35 A (Table 430.52).
- Disconnecting means: horsepower rated and at least 115% × 14 A = 16.1 A (430.110(A)).
Motor control centers, drives or a plant full of motors?
Dreiym's licensed Professional Engineers design motor circuits and feeders and coordinate their protection with the rest of the system, PE-stamped where required. Free quote; we typically respond within one business day.
Safety and limits
What this does not check: several motors on one feeder (430.24 and 430.62), motors on adjustable-speed drives (430.122, 430.130 and the drive instructions), hermetic refrigerant motor-compressors (Article 440), fire pumps (Article 695), motors over 1,000 V, voltage drop during starting, and the equipment grounding conductor (250.122(D)). Small motors under the 430.32(B) and (D) rules can have other overload options.
Screening tool: Screening estimate for education and planning. Not an engineering study or a design, and not a substitute for a licensed engineer's review where one is required.
How the calculation works
- Full-load current from Table 430.248 (single-phase) or 430.250 (three-phase) for the horsepower and voltage. It sizes the conductors and the short-circuit protection; the nameplate current sets the overload (430.6(A)).
- Conductors: ampacity at least 125% of the table current (430.22), from Table 310.16 with the ambient and adjustment factors of 310.15, and no more than the terminal column. 240.4(D) does not apply to motor circuits (240.4(G)).
- Overload: 125% of the nameplate current for a service factor of 1.15 or more or a temperature rise of 40 °C or less, 115% for other motors (430.32(A)(1)); up to 140% or 130% where that is not enough (430.32(C)).
- Short-circuit and ground-fault protection: the Table 430.52 percent of the table current. A value that is not a standard rating may go to the next standard rating (430.52(C)(1)(a)). Where that will not start the motor, 430.52(C)(1)(b) allows up to 400% for an inverse time breaker on a full-load current of 100 A or less (300% above), 225% for a time-delay fuse, 400% for a nontime-delay fuse of 600 A or less or a Class CC time-delay fuse, and 300% for a fuse of 601 to 6,000 A; the calculator shows the option that allows the most. In the 2020 edition these were Exceptions No. 1 and No. 2 to 430.52(C)(1).
- Disconnecting means: at least 115% of the table current (430.110(A)).
Table 430.52 percentages used
| Motor type | Nontime-delay fuse | Time-delay fuse | Instantaneous trip breaker | Inverse time breaker |
|---|---|---|---|---|
| Single-phase | 300 | 175 | 800 | 250 |
| Squirrel cage, other than Design B energy efficient or premium efficiency | 300 | 175 | 800 | 250 |
| Design B energy efficient or premium efficiency | 300 | 175 | 1,100 | 250 |
| Wound rotor | 150 | 150 | 800 | 150 |
Sources
Sources: NFPA 70, National Electrical Code, 2023 edition: 110.14(C)(1)(a), 240.4(G), 240.6(A), Table 310.15(B)(1)(1), Table 310.15(C)(1), Table 310.16, 430.6(A), 430.22, 430.32(A)(1) and (C), 430.52(C)(1)(a) and (b) and 430.52(C)(3) with Table 430.52(C)(1) (Table 430.52 in the 2020 edition), 430.110(A), Tables 430.248 and 430.250. Check the edition your jurisdiction enforces.
Cite or share this tool
Dreiym Engineering. Motor circuit calculator. Method: NEC 430.22, 430.32 and Table 430.52. https://www.dreiym.com/motor-circuit-calculator/
Instructors and shops are welcome to link to this tool or put its address on a handout. It is free, needs no sign-up and works on a phone.
Link copied.Citation copied.The copy did not work. The text is selected, so copy it with your device.AccessedHow to use the calculator
Choose the phase, the motor voltage and the horsepower. For a three-phase motor, pick the type; most general-purpose NEMA motors sold today are Design B premium efficiency. Enter the nameplate full-load current for the overload setting, and tick the service factor box when the nameplate shows 1.15 or more, or a temperature rise of 40 °C or less. Then pick the breaker or fuse type, the conductor material and the terminal rating.
How to size a motor branch circuit
- Look up the full-load current in Table 430.250 (three-phase) or 430.248 (single-phase). Use the table, not the nameplate, for the conductors and the short-circuit protection (430.6(A)(1)).
- Size the conductors for at least 125% of that current (430.22), from Table 310.16 with any ambient and bundling factors.
- Set the overload at 125% of the nameplate current for a service factor of 1.15 or more or a temperature rise of 40 °C or less, and at 115% for other motors (430.32(A)(1)).
- Pick the short-circuit and ground-fault device no larger than the Table 430.52 percentage of the full-load current. Where that value is not a standard rating, the next standard rating is permitted (430.52(C)(1)(a), Exception No. 1 in the 2020 edition).
- Size the disconnect at 115% of the full-load current or more, horsepower rated (430.110(A)).
Worked example
A 25 hp, 208 V three-phase Design B motor, inverse time breaker, copper conductors and 75 °C terminals:
- Full-load current, Table 430.250: 74.8 A.
- Conductors: 1.25 × 74.8 = 93.5 A. 3 AWG copper carries 100 A at 75 °C; 4 AWG carries 85 A, not enough.
- Breaker: 250% × 74.8 = 187 A. That is not a standard rating, so the next standard rating, 200 A, is permitted.
- Overload, with a service factor of 1.15 and a nameplate current of 70 A: 1.25 × 70 = 87.5 A.
- Disconnect: at least 1.15 × 74.8 = 86 A, horsepower rated.
Pick the “25 hp at 208 V” quick start in the calculator above, then enter 70 in the nameplate field to set the overload.
Why the breaker can be larger than the wire
A motor draws several times its running current while it starts. In a motor circuit the overload protects the motor and the conductors from running overloads, and the branch-circuit breaker or fuse only has to clear short circuits and ground faults. That is why Table 430.52 allows a 35 A breaker on 14 AWG conductors for a 10 hp, 460 V motor, and why the small-conductor limits of 240.4(D) do not apply (240.4(G)).
Method and sources
Full-load currents come from NEC Tables 430.248 and 430.250 for motors from 115 to 575 V running at usual speeds; the percentages from Table 430.52 (numbered Table 430.52(C)(1) in the 2023 edition); and the standard ratings from 240.6(A) as of the 2023 edition, which added 10 A for breakers; in the 2020 edition 10 A was a standard rating for fuses only. Conductor ampacities follow Table 310.16 with the factors of 310.15. The full list of sections is under the calculator.
Frequently asked questions
What size breaker for a 10 hp motor?
For an inverse time breaker: up to 35 A at 460 V three-phase (14 A full-load), up to 70 A at 230 V (28 A), and at 208 V (30.8 A) 250% is 77 A, so the next standard rating, 80 A, is permitted. A smaller breaker is fine if the motor starts reliably on it.
Nameplate current or table current?
Both. The table current sizes the conductors, the breaker or fuse and the disconnect; the nameplate current sets the overload (430.6(A)).
What if the breaker trips when the motor starts?
430.52(C)(1)(b), Exception No. 2 in the 2020 edition, allows a larger device where the Table 430.52 value is not enough to start the motor: up to 400% for an inverse time breaker on a motor of 100 A or less and 300% above that, 225% for time-delay fuses, 400% for nontime-delay fuses of 600 A or less and Class CC time-delay fuses, and 300% for fuses of 601 to 6,000 A. Check the motor and its load first; repeated trips can point to a fault.
Does this work for a motor on a VFD?
Not directly. The input conductors of a variable frequency drive follow 430.122, its short-circuit and ground-fault protection follows 430.130, and the drive’s instructions often call for specific fuses.
When to bring in an engineer
A single motor is a short calculation; a plant with motor control centers, drives and large motors needs feeders, starting studies and coordinated protection. Dreiym’s licensed Professional Engineers design motor circuits and feeders, PE-stamped where required. Related tools: the wire size calculator, the voltage drop calculator and the available fault current calculator. See our electrical design and protection coordination services, or contact us for a free quote. We typically respond within one business day.