Coordination Review of a New 2 A Fuse Below an Existing 10 A Breaker in a 24 V DC Control Circuit, Houston (2019)

A Houston technology company was adding a 2 A fuse to its control cabinets, below an existing 10 A miniature circuit breaker in a 24 V DC circuit. In December 2019 it asked us whether the two would coordinate, so that a fault downstream blows the fuse and leaves the breaker closed.

Is the fuse right for DC

On December 11 we reviewed the data sheets for both devices and the wiring schematic, and searched for more data on the fuse. The next day the client sent data on the fuse holder ferrule, which showed the fuse element is rated for DC circuits up to 32 V, so it is suitable for a 24 V circuit.

The curves

Neither device was in the library of the modeling software, so we entered both trip curves into ETAP® by hand from the published performance data. The curve of the 2 A fuse does not cross the curve of the 10 A breaker at any current: the fuse operates first on an overcurrent, and the two are well coordinated. The letter report and the plotted curves went to the client on December 12, 2019.

Related services

Larger systems get the same treatment in our protection coordination studies.