DC Arc Flash in Battery, UPS and PV Systems: How the Hazard Is Assessed

Why IEEE 1584 doesn't cover DC arc flash, how the NFPA 70E DC methods work, what a battery, UPS or PV study needs, and labels, PPE and mitigation.

By Dreiym Engineering

Subject Matter Expert: Brian J. Brackensick, M.S., P.E.

Technical review: Brian J. Brackensick, M.S., P.E.

Published 11 min read

Open battery cabinet of an uninterruptible power supplyOpen battery cabinet of an uninterruptible power supply
Contents
  1. Why DC Arc Flash Is Different
  2. Where DC Arc Flash Methods Come From
  3. What a DC Study Needs
  4. Typical DC Equipment in a Study
  5. Labels, PPE and Work Practices
  6. Reducing DC Arc Flash Hazard
  7. Common Mistakes
  8. Frequently Asked Questions
  9. How Dreiym Engineering Can Help

A DC arc flash is the burst of heat and light from an arc in a direct current circuit: a battery rack, the DC bus of a UPS, a PV combiner box or a DC switchboard. The hazard is real, but the model most arc flash studies use, IEEE® 1584-2018, covers three-phase AC systems from 208 V to 15 kV and leaves DC out. DC equipment is assessed instead with the methods summarized in Informative Annex D of NFPA® 70E (opens in a new tab), or with the standard’s DC arc flash PPE category table where the equipment falls inside that table’s limits.

Key takeaways

  1. A DC arc flash is the burst of heat and light from an arc in a direct current circuit, such as a battery rack, a UPS DC bus or a PV combiner box.
  2. An AC arc passes through current zero twice every cycle, but DC current has no zero crossing, so a DC arc can keep burning steadily.
  3. IEEE® 1584-2018 is built on three-phase AC test data and leaves DC systems out of its scope.
  4. Informative Annex D of NFPA® 70E summarizes the DC methods in use, which are usually more conservative and depend heavily on how long the arc lasts.
  5. NFPA® 70E 130.5(H) labeling applies to DC equipment the same way it applies to AC equipment.

Those DC methods are simpler than the AC model and usually more conservative, so the results depend heavily on good input data and on one assumption in particular: how long the arc lasts. Below we cover why DC behaves differently, where the methods come from, what data a study of battery, UPS and PV equipment needs, and how labels, PPE and design choices follow from the results.

Why DC Arc Flash Is Different

An AC arc passes through current zero twice every cycle, and a protective device can use those zeros to interrupt it. DC current has no zero crossing. Once a DC arc is established across a gap it can keep burning steadily, and a breaker or fuse has to force the current to zero on its own, which is why DC ratings on protective devices matter.

The sources behave differently too:

  • Batteries deliver fault current limited mainly by their internal resistance and the resistance of the cables and connections. A large stationary battery can deliver a high current for as long as it holds charge, and it can’t be switched off: opening a breaker isolates the load, but the cells stay energized.
  • PV arrays are current-limited sources. A string’s short-circuit current is only modestly above its operating current, so an arc in a PV circuit may never draw enough current to open a fuse or trip a breaker. As long as the modules are lit, the array is a source.
  • UPS systems have a DC link fed from two directions: the battery and the rectifier (or charger). Both can feed an arc on the DC bus, and capacitors on the link add a short discharge of their own.

Most published DC methods were also developed for arcs in open air. NFPA® 70E notes that if the task is inside an enclosure, the incident energy can be higher than an open-air calculation shows, because the enclosure focuses the energy toward the opening.

Where DC Arc Flash Methods Come From

IEEE® 1584-2018, Guide for Performing Arc-Flash Hazard Calculations, is built on test data from three-phase AC equipment. Its scope leaves single-phase AC and DC systems out, with some references for those applications. The revision project now under way at IEEE® (opens in a new tab) keeps the same three-phase AC scope.

For DC, Informative Annex D of NFPA® 70E summarizes the methods in use (D.5, “Direct Current Incident Energy Calculations”):

  • The maximum power method. Based on a paper by D. R. Doan in IEEE® Transactions on Industry Applications, it assumes the arc draws the most power the source can deliver. As D.5.1 puts it, the method “is based on the concept that the maximum power possible in a dc arc will occur when the arcing voltage is one-half the system voltage.” It needs only the system voltage, the available fault current and the arc duration, and because it assumes the worst case it usually gives high results.
  • Arc resistance models. Work compiled by Ammerman, Gammon, Sen and Nelson, also in IEEE® Transactions on Industry Applications, models the arc’s resistance from test data (including the Stokes and Oppenlander arc equations) and solves for the arcing current, with separate equations for an arc in open air and an arc in a box. These take more data, such as the gap between conductors, and usually give lower, more realistic results.
Left: a circuit with a DC source of voltage V and internal resistance R, connected to an arc. Right: a plot against arc current from zero to the bolted fault current. The arc voltage falls in a straight line from the full source voltage at zero current to zero at the bolted fault current. The arc power, voltage times current, is a curve that is zero at both ends and peaks at half the bolted fault current, where the arc voltage is half the source voltage. The peak power equals the source voltage times the bolted fault current divided by four. A note says NFPA 70E Annex D.5.1 bases the maximum power method on this peak, and that real arcs draw less, so the method is usually conservative.
Figure 1. The maximum power method: a DC source with internal resistance delivers the most power to an arc when the arc voltage is half the source voltage and the current is half the bolted fault current.

NFPA® 70E also gives a shortcut. Where an incident energy analysis isn’t done, the arc flash PPE category method uses Table 130.7(C)(15)(b) for DC equipment: storage batteries, DC switchboards and other DC supply sources. The table assigns a PPE category and an arc flash boundary only within stated limits of voltage, available fault current, arc duration and working distance. Outside those limits, an incident energy analysis is required. Section numbers here are from the 2024 edition; NFPA® 70E is revised every three years, so check them against the edition your electrical safety program uses.

What a DC Study Needs

The calculation is short. Collecting the data takes most of the time, and it is where most errors come from.

Source or equipmentWhat sets the fault currentWhat sets the arc durationData to collect
Stationary batteryCell internal resistance, number of cells and strings, cables and connectionsThe nearest fuse or DC breaker, if it operatesManufacturer short-circuit current or internal resistance, cell count, string arrangement, cable sizes and lengths, protective device data
UPS DC linkBattery plus rectifier or charger current limit, plus DC link capacitorsBattery breaker or fuse, UPS controlsUPS model and DC bus voltage, battery data, rectifier current limit, protective devices on the DC side
PV arrayModule short-circuit current times the number of parallel stringsOften not a protective device: the assumed exposure timeModule data sheets, string and combiner layout, fuse ratings, conductor lengths, inverter DC disconnects
DC switchboardEvery source that can feed the busMain and feeder devices with DC ratingsOne-line diagram, device types, DC trip characteristics, source data

A few points that make the difference between a useful study and a misleading one:

  • Use the manufacturer’s short-circuit data. A battery’s ampere-hour rating says how long it lasts, not how much fault current it delivers. Battery manufacturers publish short-circuit current or internal resistance, and the cable and connection resistance between the cells and the arc location has to be included.
  • Count every source. On a UPS, the battery and the rectifier can both feed the DC bus. On a DC switchboard, a battery and a charger usually feed it at the same time.
  • Be explicit about arc duration. Where a fuse or breaker will clear the arc, its DC time-current characteristic sets the time. Where nothing will clear it, as in many PV circuits, the study has to state the assumed exposure time and why.
  • Note the working conditions. Open battery racks, enclosed battery cabinets and switchboard compartments call for different calculations and working distances.
Two panels. Left, a battery string: cells feed a DC fuse and a cable to an arc. A bar compares the available fault current with the fuse's operating range: the fault current is far above the point where the fuse opens, so the fuse clears the arc and its DC time-current curve sets the arc duration. Right, a PV string: modules feed a string fuse and a cable to an arc. Bars show the operating current and the available fault current, which is only slightly higher, and both are below the point where the fuse opens, so the fuse may never clear the arc and the study has to assume an exposure time. A note says to state the arc duration and its basis for every DC label.
Figure 2. What sets the arc duration: a battery feeding a fuse can drive enough current to clear an arc quickly, while a PV string’s fault current is barely above its operating current, so its fuse may never open and the exposure time has to be assumed.

Related service

Arc Flash Studies

IEEE® 1584 incident energy and NFPA® 70E labels

Request a free quote

Typical DC Equipment in a Study

The equipment we see most often in DC arc flash work:

  • Battery rooms and racks for switchgear control, telecom, data centers and substations, where work on terminals and inter-cell connectors is done with the battery energized.
  • UPS battery cabinets and DC links, including battery breakers and the DC bus inside the UPS.
  • PV combiner and recombiner boxes, and inverter DC inputs, where several strings are paralleled and the available current adds up.
  • DC switchboards and distribution panels fed by batteries and chargers.
  • Battery energy storage systems, where the DC bus voltage and the number of parallel racks can produce high available fault current.

Most of this equipment sits next to AC equipment that already has labels from an AC study. The DC equipment needs its own analysis, and the study should say clearly which method was used for each label.

Labels, PPE and Work Practices

NFPA® 70E 130.5(H) applies to DC equipment the same way it applies to AC equipment. Equipment likely to require examination, adjustment, servicing or maintenance while energized gets a label with the nominal system voltage, the arc flash boundary, and at least one of: the available incident energy and its working distance, or the arc flash PPE category (but not both), the minimum arc rating of clothing, or the site-specific level of PPE. The data behind the label has to be documented and reviewed for accuracy at intervals not to exceed 5 years. See our post on arc flash labeling for how labels are read and kept current.

DC work has a few features AC work doesn’t:

  • Shock approach boundaries for DC come from their own table in NFPA® 70E, not the AC table.
  • Batteries add chemical hazards. NFPA® 70E notes that apparel that may be exposed to electrolyte has to be evaluated for that exposure as well as arc rated, and the standard has battery and battery room requirements in its chapter on special equipment.
  • A battery can’t be put in an electrically safe work condition by opening a switch. Work on the battery itself is energized work, so the job plan has to address both shock and arc flash, often by breaking a string into lower-voltage sections before work starts.
  • PV modules generate whenever they’re lit. Opening a disconnect de-energizes the circuits on one side of it only.

PPE categories for DC come from the DC table or from the calculated incident energy, never from the AC table. Our post on arc flash PPE categories explains what each category includes.

Reducing DC Arc Flash Hazard

The DC methods are sensitive to the same two things AC results are: available current and time. Mitigation works on both:

  • Fast, DC-rated protection close to the source. Fuses at the battery terminals or in each string, sized and rated for DC, can limit both the current and the arc duration downstream. Devices rated only for AC may not interrupt DC safely.
  • Segmenting batteries. Disconnects or links that split a string into lower-voltage sections reduce both the shock hazard and the arc flash hazard during maintenance.
  • Insulation and guarding. Terminal covers, insulated inter-tier connectors and insulated tools reduce the chance that a dropped tool starts an arc.
  • Distance. Remote operation of DC breakers, and disconnects located outside the battery room, keep people out of the arc flash boundary during switching.
  • PV protection required by the NEC®. The 2023 NEC® requires DC arc-fault circuit protection for many PV systems (690.11) and rapid shutdown of PV circuits on buildings (690.12). These reduce how long an arc can burn and how much of the system stays energized after shutdown.
  • Design-stage choices. Battery size, string arrangement, cable routing and device locations set the hazard for the life of the system. They are cheaper to change on a drawing than in an installed battery room.

Common Mistakes

  1. Running DC equipment through an AC model. IEEE® 1584-2018 equations, and AC calculators built on them, don’t apply to DC. Our arc flash calculator is an AC tool for the same reason.
  2. Using the battery’s ampere-hour rating instead of the manufacturer’s short-circuit current or internal resistance.
  3. Leaving out the rectifier or charger on a UPS or DC switchboard.
  4. Assuming a PV fuse will clear an arc that draws little more than the string’s operating current.
  5. Applying an AC PPE category to DC equipment.
  6. Not updating the study when batteries are replaced with a different size, chemistry or string arrangement.

Frequently Asked Questions

Does IEEE® 1584-2018 cover DC arc flash?

No. IEEE® 1584-2018 covers three-phase AC systems from 208 V to 15 kV. DC systems are outside its scope, and DC incident energy is calculated with the methods summarized in NFPA® 70E Informative Annex D.

Can we use the NFPA® 70E DC table instead of a calculation?

Yes, where the equipment is within the table’s limits for voltage, available fault current, arc duration and working distance. You still need the available fault current and the clearing time to show that it is. Outside those limits, an incident energy analysis is required.

Why is our DC result higher than the AC result on nearby gear?

The common DC methods, especially the maximum power method, are deliberately conservative, and many DC sources have no protective device that clears an arc quickly. A more detailed method, better source data or faster DC protection usually lowers the result.

Does a PV combiner box need an arc flash label?

If it is likely to be examined, adjusted, serviced or maintained while energized, NFPA® 70E calls for a label. Combiner and recombiner boxes are often opened for testing and troubleshooting, so they are usually included in the study.

How often should a DC arc flash study be reviewed?

NFPA® 70E requires the label data to be reviewed for accuracy at intervals not to exceed 5 years, and sooner when the system changes, such as a battery replacement, a new UPS or added PV strings.

How Dreiym Engineering Can Help

We perform arc flash studies for AC and DC systems, including battery, UPS and PV equipment, together with the short circuit analysis and protective device coordination studies they rely on, modeled in ETAP® and SKM. Our electrical power studies are led by Brian J. Brackensick, M.S., P.E., with field data collection by Ruben A. Rodriguez. We print and install arc flash labels or ship them to you, and we offer training on IEEE® 1584-2018 and NFPA® 70E. Reports are stamped by a licensed Professional Engineer where required. Contact us or call (866) 621-6920 for a free quote. We typically respond within one business day.

Discussion

Comments are reviewed before they appear. We cannot give opinions on specific incidents or cases in comments.

We also teach NFPA® 70E and IEEE® 1584-2018 to electricians and engineers, built around the labels from your own arc flash study. Electrical safety training →

Talk to an engineer about your project

We typically respond within one business day.

Request a free quoteor call (866) 621-6920

Newsletter

Engineering notes from Dreiym

New articles on power systems, corrosion and forensic engineering, by email when we publish. Free account included: keep your calculator work, reports and exports in one place.

Latest article: DC Arc Flash in Battery, UPS and PV Systems: How the Hazard Is Assessed

One email per new article. Unsubscribe in one click.

You are subscribed: new articles come to you by email.

Manage in My account