Galvanic Cathodic Protection Design and As-Built Record for Underground Condenser Water Piping at a Military Installation, Central Texas (2025)
An HVAC upgrade at a building on a military installation in Central Texas brought new underground condenser water piping, an 8-inch supply line and an 8-inch return line. As part of the design-build team, we designed the cathodic protection, issued for construction in January 2025, supplied its materials, and recorded the installed system on an as-built sheet in November 2025.
Sizing the anodes
The calculation covers about 400 feet of 8-inch pipe with a closed-cell foam jacket in soil of about 1,000 ohm-cm, or about 838 square feet of pipe surface. Assuming 10 percent of the jacket fails over a 25-year life, about 84 square feet of bare steel would need 2 mA per square foot, about 0.17 A. With magnesium delivering 0.125 amp-years per kilogram and a utilization factor of 0.85, the minimum anode weight came to 87 pounds. The design uses six prepackaged high-potential magnesium anodes of 17 pounds each, 102 pounds in all.
Test points and isolation
Two test stations, one at each end of the run, serve both lines, and one of them is set in the building slab. They carry the structure wires, a buried reference electrode with a coupon, and a current shunt for reading anode output. Insulating flange kits at the first flange above grade on each end, furnished by others, isolate the buried pipe from the building piping and grounded supports. The general notes require a corrosion engineer to inspect and test the installation and to report the potentials, anode currents and flange test results.
Related services
The method is described under cathodic protection design, and the testing after installation under start-up and commissioning.
Corrosion and CP
Related projects
Dallas, TX
Hot Water Piping CP Design and Start-Up at a Wastewater Plant, Dallas
CP design, commissioning
El Paso, TX
Power Station Impressed Current CP, El Paso
CP design, installation
Sweeny and Baytown, TX
Process Plant CP Design and Commissioning, Sweeny and Baytown
CP design, commissioning
More work in: Texas
Get your project started
We typically respond within one business day.