Selected Projects
Electrical Design for EV Charger Panels on Three Garage Levels of a Condominium Building, San Antonio (2021 to 2022)
We typically respond within one business day.
Project at a glanceDE-PRJ-10848
- Practice
- Electrical power
- Location
- San Antonio, TX
- Service
- EV charging, electrical design
- Client
- Confidential
Electrical Design for EV Charger Panels on Three Garage Levels of a Condominium Building, San Antonio (2021 to 2022)
A condominium building in San Antonio wanted EV charging on three of its garage levels. We designed the electrical addition, issued it for review in November 2021, revised the layout in December and issued it for construction in January 2022.
Capacity first
The building service could give the chargers no more than 83 kVA of coincident load, which is 100 A at 480 V or 230 A at 208 V. The design is built around that limit, and the notes require engineering supervision for any load added beyond what the drawings show.
The design
A new 125 A breaker in a 480 V, 225 A building service panel feeds a 112.5 kVA dry-type transformer on the floor of the garage electrical room, stepping down to 208Y/120 V. Its secondary feeds three 200 A disconnects, each fused at 125 A, and each disconnect feeds a 208 V, 200 A EV panel on its own garage level. The notes also call for the transformer output tap to be raised at least 5 percent during commissioning, and treat the conduit sizes shown as minimums.
Related services
Capacity checks like this one are part of our load analysis, and the drawings of our electrical design services.
Electrical power
Related projects
Dallas, TX
200 A Lot Upgrade Design for a Manufactured Home Community, Dallas
Load analysis, feeder sizing
Dayton, Strawn and San Antonio, TX
RV Park Service and Feeder Sizing in Dayton, Strawn and San Antonio
Load analysis, feeder sizing
Austin, TX
EV Charging Capacity Studies, Austin
EV charging, load studies