Load Analysis and Feeder Design for 200 A Lot Upgrades at a Manufactured Home Community, Dallas (2019 to 2020)

We typically respond within one business day.

Project at a glanceDE-PRJ-10847

Location
Dallas, TX
Service
Load analysis, feeder sizing
Client
Confidential

Load Analysis and Feeder Design for 200 A Lot Upgrades at a Manufactured Home Community, Dallas (2019 to 2020)

The owner of a manufactured home community in Dallas planned to bring its lots up to 200 A service. From June 2019 to August 2020 we issued six interim review sets of the electrical design for the upgrade.

Sizing for diversity

The load summary treats each 200 A lot as 47.8 kVA connected and applies a demand factor of 0.24 across 26 lots, for 299 kVA. A 48 kVA community panel, for loads such as the pool, brings the design load to 347 kVA, or 1,446 A at 240/120 V. Homes do not all draw their full load at once, and the demand factor keeps the service and the feeders to a practical size.

The distribution

The design takes the service from a utility transformer through a 1,600 A fused main. Six fused 350 A feeders of 300 kcmil aluminum, run overhead in free air for up to 520 feet, each serve a group of lots with demand loads of 263 to 329 A, and a 200 A feeder serves the community panel. Overhead taps drop from each feeder to the main breaker of each home, and the notes cap a home main breaker at 200 A.

The sets on file are interim review drawings marked not for construction.