Fall-of-Potential Ground Resistance Tests at 101 Points for a New Distribution Center, San Antonio (2015)

A new distribution center in San Antonio needed its grounding checked before it went into service. Over three days in spring 2015 we measured the ground resistance at 101 test points with the fall-of-potential method.

How the readings were taken

At the first point we ran a full profile, moving the potential probe from 10 to 90 feet out from the ground rod. The resistance climbed only from 3.14 to 3.47 ohms over that distance, and between 50 and 70 feet it held at 3.29 ohms. For every point after that we took readings with the probe at 58, 60 and 62 feet and recorded the deviation between them. In almost all cases the three readings matched or differed by less than 1 percent, which indicates the probe was outside the influence of both the rod and the current electrode. For each point we also logged the date of the last rain: 7 days before the March 28 tests, 13 days before April 3 and 15 days before May 2.

Results

Readings ranged from 0.605 to 41.2 ohms. Seventy-six of the 101 points measured 5 ohms or less, and only one exceeded 25 ohms, the 41.2-ohm reading taken on May 2, the driest of the three test days. The table of all 101 points, with the three probe readings, the deviation and the rainfall data, was the commissioning record.