Recurring Grounding Survey and Infrared Scan Program, Texas Hill Country (2024-2025)

Under a recurring grounding and infrared program, we made regular visits to facilities in the Texas Hill Country in 2024 and 2025 to survey their grounding and scan their electrical equipment with an infrared camera. We keep client details confidential.

Thermal imaging inspection of electrical equipment

An infrared inspection of electrical equipment. A thermal camera can’t see through a closed door, so the covers have to come off or IR windows have to be fitted.

Corroded grounds and loose connections

Ground electrodes corrode and terminations work loose without anyone seeing it happen, and an overloaded circuit is just as hard to spot. None of it gives a warning until something fails hot. Catching these problems on a survey costs far less than finding them after a failure.

Why the two surveys go together

A grounding survey checks that the system’s connection to earth is still there, at the resistance the design assumed, and that the bonding between pieces of equipment is intact. An infrared scan reads temperature instead. Under load, a loose or corroded connection runs hotter than its neighbors, and the camera finds that hot spot before it turns into a failure or a fire. Infrared cameras only read surface temperature and can’t see through a closed metal panel door, so qualified personnel take the covers off for the scan, or it’s done through installed infrared windows. Between them, the two surveys cover the faults that are hardest to see.

Measuring ground resistance by fall of potential

IEEE® Std 81 describes fall of potential, the reference method for measuring the resistance of a grounding electrode system to earth. Current is driven between the electrode under test and a remote current probe, and the potential is measured at a series of points in between. Plot those readings against distance and they level off on a plateau, where the resistance areas of the two electrodes no longer overlap. The value on that plateau is the system’s resistance. The familiar shortcut is to take a reading at 62 percent of the distance to the current probe. That only lands on the plateau when the probe is far enough out and the soil is reasonably uniform. With a large or irregular grid, the shortcut can give a reasonable-looking number that’s wrong.

Two things complicate this in the field all the time. If the electrode is bonded to a multi-grounded system, the meter isn’t reading that electrode by itself. Either the electrode gets isolated for the test, or the branch you’re interested in is read with a selective or clamp-on method. Soil moisture moves the result too. The same electrode can read quite differently after a rain than at the end of a dry summer, which is why the season and conditions get written down with the number. Recorded that way, each year’s readings can be compared with the last, and a trend shows up.

Bolted equipment in a false color thermal frame, orange with a magenta band at left and a yellow-white hot spot on wires

A false color thermal frame showing localized heating. Infrared surveys are run with equipment in normal service, because a component that isn’t carrying load reads close to ambient and shows nothing.

Doing an infrared scan properly

A thermal camera only reads surface temperature, which limits the survey more than most people expect. The equipment has to be under representative load. A connection that will run hot at full load can look perfectly normal at a quarter of it. The camera can’t see through a closed metal enclosure. Either qualified personnel have to take the covers off, wearing the protection the energized work task requires, or infrared windows have to be installed so the scan can be done with the doors shut. Emissivity and reflected energy have to be accounted for as well. Get them wrong and a shiny bus bar will report a temperature it doesn’t have.

The most useful result comes from comparing readings. Three phases of the same circuit carrying similar current should run at similar temperatures. The difference between them is what points to a developing problem, and its size tells you how urgent it is. Findings get ranked by severity instead of going out as a flat list, so the work that matters most gets done first. Repeating the survey on a schedule turns single readings into trends and catches connections that are getting worse as well as the ones already close to failing.

Keeping a record from one year to the next

We ran both surveys on a recurring schedule and documented the results year to year, so trends showed up before failures did. Licensed Professional Engineers reviewed the findings, which went out with the corrections ranked by priority.

Planning maintenance around the surveys

Regular inspections put electrical maintenance on a schedule. Without them, it gets done after something fails. Our grounding system testing and infrared inspection services pages say more about each survey, and our guide to loose electrical connections explains how to avoid them.