Annual Energy Use Estimate for an Administration Building and an Office Trailer at a Chemical Plant, Pasadena (2019)

A chemical plant in Pasadena needed to know, for budgeting, how much energy its administration building and an office trailer used each year. Neither had a meter of its own, and the plant as a whole had reported about 81.3 million kWh for the year. In January 2019 we prepared a professional estimate.

How we estimated

The only sure answer comes from measurement with metering suitable for revenue use. Without it, we worked from information the plant provided, including an arc flash study we had done there earlier, which showed the administration building fed through a 480 V, 800 A breaker. We used 30 kWh per square foot per year, the figure the US Energy Information Administration gives for general offices, within its range from 7 kWh for vacant buildings to 82 kWh for food service.

The result

At 11,100 square feet, the administration building came to about 333,000 kWh a year. At 4,800 square feet, the trailer came to about 144,000 kWh. Server rooms, the age of a building, kitchens, staffing, HVAC practice, shutdowns and weather all move the real figure, so we recommended metering if those differences mattered to the budget.