What Is an Open Neutral? Symptoms, Dangers and a Live Demo

An open neutral can push half a home's circuits far above 120 V. See what it means on an outlet tester, the symptoms, what to do and a live demo.

By Dreiym Engineering

Subject Matter Experts: Brian J. Brackensick, M.S., P.E. and Stepan V. Eero, M.S., P.E.

Published Updated 12 min read

Simplified drawing of an open neutral on a 120/240 V service: with the neutral broken, the 1,440 W load on L1 drops to 48 V and the 360 W load on L2 rises to 192 VSimplified drawing of an open neutral on a 120/240 V service: with the neutral broken, the 1,440 W load on L1 drops to 48 V and the 360 W load on L2 rises to 192 V
Contents
  1. What is an open neutral?
  2. Open neutral symptoms and the warning signs of a loose neutral
  3. How a 120/240 V split-phase service works
  4. What happens when the neutral opens
  5. Open the neutral yourself in our simulator
  6. What causes an open neutral, and where it fails
  7. What to do if you suspect an open neutral
  8. Investigating an open neutral for attorneys, insurers and adjusters
  9. Frequently asked questions

If the neutral feeding a house breaks, half the circuits can run far above 120 V while the rest sag. That’s an open neutral. It can damage many appliances at once. The failing connection can overheat, and current can end up on the water pipes. A plug-in tester that reads “open neutral” at one outlet usually means a fault on just that circuit, which we cover below.

Unfamiliar terms? See the Engineering Glossary

If you think you have an open neutral, call your electric utility or a licensed electrician now. Don’t open the meter base or take the panel cover off, and stay away from anything that gives you a tingle.

Jump to the symptoms, what to do, the live simulator or investigating a loss.

What is an open neutral?

An open neutral is a break in the neutral wire somewhere between the utility transformer and your main panel. On a 120/240 V service, the neutral is what holds each half of the house at 120 V. Without it, the 120 V loads on the two legs end up in series across 240 V, and one half of the house runs high while the other runs low.

You’ll also hear electricians call it a lost neutral, a broken neutral or a floating neutral. A portable generator’s “floating neutral” is something else. A loose neutral is the same fault at an earlier stage: the connection still touches, just not very well.

What “open neutral” means on an outlet tester

A plug-in tester showing “open neutral” at one outlet means that branch circuit’s neutral is broken. The break could be at the receptacle, a splice upstream or back at the panel. Usually only that circuit is affected. The exception is a multiwire branch circuit, where two circuits share one neutral (2023 NEC 210.4). A break in that neutral does to both circuits what an open service neutral does to the house. Even when it’s just one circuit, a failing connection still heats up, so stop using the circuit and call a licensed electrician. Our guide to loose electrical connections explains why. A tester checks wiring, not voltage, so a normal reading doesn’t rule out a problem with the service neutral.

Open neutral symptoms and the warning signs of a loose neutral

Loose neutral symptoms come and go as the connection makes and breaks contact. Once the neutral breaks completely, they stop coming and going, though they still change as appliances turn on and off. What to watch for:

  • Lights getting brighter in some rooms and dimmer in others, especially when a microwave, heater or washer kicks on or off.
  • Several electronics or appliances failing at once. Surge strips may fail or smell hot too.
  • Electronics resetting, a UPS switching to battery, or motors that hum and struggle.
  • A tingle when you touch a faucet, sink, tub or the frame of an appliance.
  • Crackling, buzzing or a burning smell at the meter or the panel.
  • A sagging service drop, or damage after a storm, a fallen limb or a vehicle strike.
  • Your neighbors on the same transformer are seeing the same thing.

Breakers rarely trip, because the loads themselves limit the current. That’s why an open neutral can go on for days. If half the house goes dead instead, you’re usually looking at a lost hot leg (see the FAQ).

How a 120/240 V split-phase service works

The utility transformer, on a pole or in a pad-mounted box, has a secondary winding tapped at its center. That center tap is the neutral (N). The ends of the winding are the hot legs, L1 and L2, and each measures 120 V to the neutral. They’re half a cycle apart (0° and 180°), so you measure 240 V from L1 to L2.

Lights, receptacles and most appliances run from one leg to the neutral at 120 V. Water heaters, air conditioners and EV chargers go across L1 and L2 at 240 V. Ranges and dryers use both: 240 V for heat, and 120 V for controls, lamps and motors. Many apartments have 120/208 V service instead, where an open neutral works the same way with different numbers.

Does the neutral wire carry current?

Yes. On a branch circuit, the neutral carries all of that circuit’s current. On the service it carries the difference between the 120 V currents on the two legs, not their sum, so with 12 A on L1 and 3 A on L2 it carries 9 A. It also ties the house neutral to the transformer’s center tap, so each leg stays near 120 V.

Is the neutral the same as ground?

No. The neutral carries current in normal operation, while the equipment grounding conductors (the bare or green wires) are only meant to carry current during a fault. Inside the house the two are joined in just one place, at the service. That’s also where the neutral connects to the ground rod and the bonded metal water pipe (2023 NEC 250.24 and 250.104(A)(1)).

What happens when the neutral opens

With the neutral broken, current flows from L1 through the L1 loads, across the neutral bar and through the L2 loads to L2. The two groups are now in series across 240 V and split it in proportion to their resistance:

V(L1) = 240 V × R1 ÷ (R1 + R2)
V(L2) = 240 V × R2 ÷ (R1 + R2).

The leg with less load has the higher resistance, so it takes the bigger share and rises above 120 V, while the heavily loaded leg sags. Using rated watts at 120 V instead, V(L1) = 240 V × P2 ÷ (P1 + P2).

A worked example

Here’s the example from our simulator: 1,440 W on L1 (10 Ω) and 360 W on L2 (40 Ω), both rated at 120 V.

QuantityNeutral intactNeutral open
L1 load, 1,440 W rated120 V, 12 A48 V, 4.8 A, 230 W
L2 load, 360 W rated120 V, 3 A192 V, 4.8 A, 922 W
Neutral9 A0 A, 72 V across the break
L1 to L2240 V240 V
Resistive loads, complete break, no earth path.

With the neutral open, the same 4.8 A flows through both loads (240 V ÷ 50 Ω). Power goes up with the square of the voltage, so the 360 W load, now at 192 V, dissipates 922 W. That’s 2.56 times its rating.

How much ANSI C84.1 lets the voltage vary from 120 V

ANSI C84.1 (Table 1) puts Range A for a 120/240 V service at 114 to 126 V per leg. Range B, 110 to 127 V, is only tolerated for limited periods. Now suppose the neutral is fully open with no earth path, and use Range A as a yardstick for the loads. Both legs stay inside it only if the load split falls between 47.5% and 52.5%. An ordinary household imbalance puts at least one leg outside that band, often far outside.

When some current returns through the earth

Real open neutrals are often milder than the worked example. Some current gets back through the ground rod and soil, and through water pipes shared with neighbors. Bonded cable TV shields carry some too (2023 NEC Chapter 8). With one 25 Ω ground rod, our example comes out at about 65 V and 175 V, and about 2 A flows in the grounding electrode conductor. A metal water main can cut the swing to a few volts, but it may carry several amperes doing it.

The NEC doesn’t rely on the earth to clear faults. In its words, “The earth shall not be considered as an effective ground-fault current path” (2023 NEC 250.4(A)(5)). An open neutral pushes current through the earth anyway. The grounded metal in the house ends up tens of volts above the utility’s neutral, about 55 V in our example. That’s how someone at a faucet or a cut pipe can get shocked. See our articles on grounding and bonding and the Ufer ground.

Open the neutral yourself in our simulator

The simulator below models the same service, with a heavy load on L1 and a light load on L2. In the “Open neutral explained” panel, switch the Neutral between Intact and Open, then change the loads and tick “Earth path” to see how the voltages move. It’s a teaching model built from ideal resistors, not a diagnostic tool. Real electronics and motors can behave worse, and LED lamps may not show the brightening. There are more examples in our online circuit simulator.

Live circuit simulator

Open neutral (120/240 V split phase)

It runs in your browser and loads when you open it. Change any part and every voltage and current updates.

Related service

Forensic Consulting

Expert reports for attorneys, insurers and owners. Consulting-only retentions are accepted.

Submit an assignment

What causes an open neutral, and where it fails

The numbered points on the service drawing above are where neutrals usually fail:

  1. The transformer or pole, at the neutral connection or one of the secondary splices.
  2. The drop or lateral, at the connectors on the house or an overhead splice. Underground, a neutral nicked during digging can corrode through.
  3. The meter base, where the neutral lug can work loose or oxidize. The neutral usually bypasses the meter itself.
  4. The main panel, at the main neutral lug or the neutral bar, especially with aluminum conductors that weren’t torqued to specification.

The usual causes are under-tightened connections, corrosion, storms, trees, vehicle strikes and plain age. On the house side, so are connectors that aren’t identified for aluminum (2023 NEC 110.14). A joint that’s gone resistive heats up and oxidizes further. With our example loads, a 1 Ω neutral joint dissipates about 64 W, enough to damage the connection before it opens.

Who is responsible, the utility or the owner?

The National Electrical Safety Code (NESC, IEEE C2) covers the utility’s facilities up to the service point (Rule 011B). The National Electrical Code (NEC, NFPA 70) defines the service point in Article 100 and covers the premises wiring past it. Each utility’s rules say where that point is. Usually the utility owns the transformer, drop and meter, and the owner owns the meter base and panel, though underground laterals vary. Each side repairs its own equipment. Who pays for damage is a separate question that depends on where and why the neutral failed, and on tariff and policy terms.

What to do if you suspect an open neutral

  • Call the utility’s outage or emergency line first, since many of these failures are on the utility’s equipment.
  • Then call a licensed electrician for the house side, and follow their advice about the main breaker.
  • If anyone has felt a tingle, keep people and pets away from the plumbing fixtures. If anything smokes, sparks or feels hot, get out and call 911. Treat a sagging or fallen drop as energized.
  • Stop using anything that has failed, and don’t count on surge strips to protect the rest. Sustained overvoltage can destroy them.
  • Hang on to whatever failed. Photograph it where it is, and ask the crews to keep the parts they replace.

Don’t open the meter base, take off the panel cover or touch the service conductors, and don’t disconnect a ground wire or a metal water pipe either. The main lugs stay live even with the main breaker off. The grounding system may also be carrying neutral current, possibly from a neighbor’s service. Your main breaker does nothing to stop that.

What the utility and your electrician will check

The utility’s crew will measure each leg to neutral, check its drop or lateral and the transformer connections, and repair its side. The utility may also disconnect a hazardous customer-side fault until it’s fixed.

Your electrician will measure each leg to neutral at the panel while putting a known 120 V load on one leg. If the neutral is bad, one leg goes up as the other goes down. They’ll also compare the current on the grounding electrode conductor and water-pipe bond with the current on the service neutral, and tighten the terminals to the manufacturer’s torque (2023 NEC 110.14(D)).

Investigating an open neutral for attorneys, insurers and adjusters

When several appliances fail together, or a fire starts at a service connection, the questions become forensic. The first is whether it was an open neutral at all. It could have been lightning or a utility surge, a primary-to-secondary contact or a lost hot leg. A neighbor’s open neutral or a shared branch-circuit neutral can look much the same. If it was the neutral, where, why and when did it fail? Whose equipment was it, and did it cause the claimed damage?

Preserve the evidence before the repair

The repair usually destroys the evidence, because crews replace the failed connector the same day. Send preservation requests as soon as a claim looks possible; counsel can advise on the duty to preserve. Ask the utility to hold the removed connectors, the drop or lateral section and the meter, along with its trouble tickets, work orders, photographs and meter data. Ask the electrician to keep any lugs they remove, and keep every damaged appliance. We document the scene as we find it, without disturbing connections. We keep a chain of custody and give all interested parties notice. As-found torque readings, disassembly and destructive tests wait until there’s an examination every party can attend. We follow ASTM E1188 and ASTM E860 and, for fires, NFPA 921.

What we look at

  • Why the connection let go: mechanical overload from a tree or ice load, wind-vibration fatigue, corrosion or heating at a high-resistance joint. Microscopy and, where needed, lab work (SEM/EDS, X-ray or CT of compression connectors) tell them apart, with the parts checked against exemplars and the maker’s specification.
  • We map each damaged item to its breaker, its leg and what was running at the time. An open neutral should show up as overvoltage damage to 120 V equipment on the lighter-loaded leg and low-voltage effects (motors, compressors) on the heavier one. Purely 240 V loads such as water-heater elements are spared, though range and dryer controls run at 120 V and can fail. Because the high leg can change as loads cycle, we check damage on both legs against the timeline. Lightning and utility surges look different: they tend to hit both legs, 240 V equipment and anything with a cable, antenna or phone connection.
  • Signs of current on the earth path, such as heated coax, arcing at pipe joints or an overheated grounding conductor.
  • We also go through the records: trouble tickets, complaints, and meter interval and event data for the address and its transformer neighbors, plus storm, inspection and vegetation records and permits. Where the NESC is adopted, defects not promptly corrected must be recorded until they are (Rule 214A4 overhead, Rule 313A underground).

One caution about meter data: a standard residential meter measures the 240 V between the legs. That stays normal during an open neutral, so normal meter voltages don’t rule one out. Responsibility depends on where and why the failure happened, the codes then in force, and the tariff and policy terms.

Our forensic electrical engineers investigate open-neutral failures, appliance damage and fires at service connections for attorneys, insurers and adjusters. To retain us on a loss, submit a forensic assignment or request an expert CV and rate schedule.

Frequently asked questions

Is an open neutral dangerous?

Yes. It can push 120 V equipment far past its rating and overheat the failing connection, and it can put current on the water pipes. Treat it as a shock and fire hazard.

Can an open neutral cause a fire?

It can. A failing neutral joint gets hotter as its resistance rises, and the overvoltage on the high leg can overheat equipment and surge strips. If there’s smoke, sparks or heat, call 911.

Why does half my house have no power?

That’s usually a lost hot leg, not a lost neutral. The 120 V circuits on that leg go dead or run very dim, and 240 V appliances won’t work properly. Call the utility or an electrician.

Will insurance cover damage from an open neutral?

That depends on the policy, and on where and why the neutral failed. Keep the damaged items and any parts that were replaced, and see investigating an open neutral above.

Codes cited: the 2023 NEC, the 2023 NESC and ANSI C84.1-2020. Your jurisdiction may have adopted a different edition.