Per-Unit Calculator for Three-Phase Fault Current

Impedances on one per-unit base, a change-of-base converter, and the three-phase bolted fault current of a radial one-line, with every step shown.

Tool referenceDE-TOOL-9174

Method
Per unit, positive sequence
Elements
Utility, transformers, cables, reactors, motors
Output
Bolted three-phase fault current and X/R

This per-unit calculator puts the utility, transformers, cables, reactors and motors of a three-phase system on one base and gives the bolted fault current at the bus you choose, with every step shown. It also converts an impedance between ohms, percent and per unit and moves it to a new base. In the worked example, a 500 MVA utility at 13.8 kV, a 1,500 kVA transformer at 5.75%, 100 ft of four sets of 500 kcmil copper and 500 hp of motors give 28.72 kA at 480 V, with an X/R of 4.79.

Per-unit calculator for three-phase fault current

Convert impedances between ohms, percent and per unit, change their base, and build a simple radial one-line from the utility to a fault. The calculator puts every element on one base, adds them in series, adds motors at the fault bus in parallel, and gives the three-phase bolted fault current with each step shown. Pick a quick start or enter your own system; the answer updates as you type.

The calculator needs JavaScript. The formulas, a worked example and the assumptions are on this page.

Quick start Fills in the form. Change anything after.

Tool and system base
Work out

The one-line gives the bolted three-phase fault current at a bus. The base converter turns one impedance into ohms, percent and per unit on the system base.

Any MVA works, because the per-unit values and the base current change together. 100 MVA is the common choice for utility and plant studies, and 10 MVA keeps numbers readable in small systems.

100 MVA is the usual choice. The answer in amps does not depend on it.

Utility source

The nominal line-to-line voltage where the utility data applies, for example 13.8 or 12.47 kV. It is also the base voltage of the first zone; every transformer then sets the base of the next zone by its voltage ratio.

Available fault level given as

Ask the utility for the available three-phase fault current (kA) or short-circuit MVA and the X/R ratio at your service point. "Infinite" leaves the source out, which gives the highest current a transformer can deliver.

The ratio of reactance to resistance of the utility system at your service point, from the utility. It sets how R and X of the source are split; it does not change the source impedance magnitude.

Elements in series, source to fault

List the equipment in order from the source to the fault, up to six. Transformers use their nameplate %Z and X/R on their own kVA and voltage ratings. Cables use R and X of one conductor (line to neutral), for example from NEC® Chapter 9, Table 9, divided by the number of parallel sets. Reactors use their ohms and X/R.

Element 1
Element 2

Ohms per 1,000 ft of one conductor, line to neutral, for example from NEC Chapter 9, Table 9.

Fault location and motors

Bus 0 is the source terminals; bus 1 is after element 1, and so on. Elements past the fault are drawn grey and left out of the sum.

Motor size in

Running induction motors feed the fault for a few cycles. Enter the total connected motor load at the fault bus. One hp is taken as about 1 kVA. When the motor data is not known, a subtransient reactance of 0.25 per unit is used, about four times full-load current, the same value as in the available fault current calculator.

Result

28.72 kA at bus 2, 0.48 kV

A bolted three-phase fault at bus 2 (0.48 kV) draws 28.72 kA symmetrical, X/R 4.79, or 23.9 MVA. The impedance at the fault is 0.8556 + j4.1 per unit. The source path gives 26.13 kA and the motors 2.58 kA.

Bolted fault at bus 2, 0.48 kV
28.72 kA sym.
X/R at the fault
4.79
Fault level
23.9 MVA
Z at the fault
4.189 pu
One-line from the source to the faultOne-line with 2 elements. Fault at bus 2, 0.48 kV: 28.72 kA.UtilityT11,500 kVA, 5.75%C2100 ftM28.72 kA at 0.48 kV
Source at the left, elements in order, the fault bus marked in orange. Motors, when included, are drawn at the fault bus. Elements past the fault are grey.

Screening estimate. Balanced three-phase bolted fault on a radial system, prefault voltage 1.0 per unit, motors as subtransient only. Equipment duty, arc flash and protection settings need a full model: see our short circuit study, or ask an engineer.

Full results and steps
ElementGivenBase kVZbase ΩR ΩX ΩR puX pu
Source500 MVA, X/R 1513.81.9040.025340.380.01330.1996
T11,500 kVA, 5.75%, X/R 6, 13.8 to 0.48 kV13.81.9041.27.2010.63023.781
C20.029 + j0.048 Ω per 1,000 ft, 100 ft, 4 set(s)0.480.0023040.0007250.00120.31470.5208
Path to bus 2Series sum0.480.0023040.0022080.010370.95824.502
Motors500 hp, X"d 0.25, X/R 6, 0.46 kV0.480.0023040.017630.10587.65345.92
At the faultPath in parallel with motors0.480.0023040.0019710.0094470.85564.1
BusBase kVIbase kAZ path puX/RkA
Bus 013.84.180.0133 + j0.199615.0020.92
Bus 10.48120.280.6435 + j3.9816.1929.83
Bus 20.48120.280.9582 + j4.5024.7026.13
  1. Base: 100 MVA and 13.8 kV at the source. Zbase = kV² ÷ MVA = 1.904 Ω; every zone after a transformer has its own base.
  2. Source: Z = 100 ÷ 500 = 0.2 pu; with X/R 15, R = Z ÷ √(1 + X/R²) = 0.0133 and X = 0.1996 pu.
  3. T1: 5.75% at X/R 6 is 0.009453 + j0.05672 pu on its own rating; × (13.8 ÷ 13.8)² × (100 ÷ 1.5) = × 66.67 gives 0.6302 + j3.781 pu.
  4. T1: next zone base = 13.8 × 0.48 ÷ 13.8 = 0.48 kV.
  5. C2: (0.029 + j0.048) Ω per 1,000 ft × 100 ÷ 1,000 ÷ 4 sets = 0.000725 + j0.0012 Ω; ÷ Zbase 0.002304 Ω = 0.3147 + j0.5208 pu.
  6. Series sum to bus 2: 0.9582 + j4.502 pu, |Z| = 4.602 pu.
  7. Motors: 500 hp taken as 500 kVA.
  8. Motors: X"d 0.25 with X/R 6 is 0.04167 + j0.25 pu on their own rating; × (0.46 ÷ 0.48)² × (100 ÷ 0.5) = × 183.7 gives 7.653 + j45.92 pu.
  9. Motors in parallel with the path: Z = Zpath × Zmotor ÷ (Zpath + Zmotor) = 0.8556 + j4.1 pu.
  10. Base current at the fault bus: 100 ÷ (1.732 × 0.48) = 120.28 kA.
  11. Fault current: 1.0 ÷ 4.189 = 0.2387 pu × 120.28 kA = 28.72 kA symmetrical.
  12. X/R at the fault: 4.1 ÷ 0.8556 = 4.79.
  13. Fault level: 100 MVA ÷ 4.189 = 23.9 MVA.
  14. Contributions: 26.13 kA from the source and 2.58 kA from the motors (plain sum 28.72 kA). Added with their angles, the total is 28.72 kA.

Need fault currents for a real system?

Dreiym's licensed Professional Engineers model the whole system in a short circuit study, check every device's interrupting and withstand rating, and carry the results into arc flash and coordination studies, PE-stamped where required. Free quote; we typically respond within one business day.

Assumptions and limits

Assumptions: balanced three-phase fault, positive sequence only; prefault voltage 1.0 per unit of the bus base voltage; bolted fault, no arc or fault resistance; load current ignored; motors as their subtransient impedance only, at the fault bus; radial series path; transformer taps at the rated voltages entered; symmetrical current only, without the DC offset or the decay over time.

What this does not check: line-to-ground, line-to-line and double line-to-ground faults; generators and other sources besides the utility; looped or networked systems; load flow; capacitor discharge; equipment interrupting and withstand ratings; arc flash.

Screening tool: Screening estimate for education and planning. Not an engineering study or a design, and not a substitute for a licensed engineer's review where one is required.

How the calculation works
  • Base impedance and current: Zbase = kV² ÷ MVA (ohms) and Ibase = MVA ÷ (1.732 × kV) (kA), with kV the line-to-line base voltage of the zone.
  • Ohms to per unit: Zpu = Z ohms ÷ Zbase. Percent to per unit: divide by 100.
  • Change of base: Zpu new = Zpu old × (kV old ÷ kV new)² × (MVA new ÷ MVA old). R and X are converted separately.
  • From Z and X/R: R = Z ÷ √(1 + (X/R)²) and X = R × X/R.
  • Utility source: Z = MVA base ÷ short-circuit MVA, where short-circuit MVA = 1.732 × kV × kA.
  • Each transformer sets the base voltage of the next zone: kV next = kV base × secondary rating ÷ primary rating.
  • Series elements add as R + jX. Motors at the fault bus are in parallel: Z = Z1 × Z2 ÷ (Z1 + Z2).
  • Fault current: I = 1.0 ÷ |Z| per unit, times Ibase at the fault bus. Fault MVA = MVA base ÷ |Z|. X/R at the fault = X ÷ R of the total.
Sources

Sources: IEEE Std 3002.3-2018, Recommended Practice for Conducting Short-Circuit Studies and Analysis of Industrial and Commercial Power Systems; J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th edition (per-unit system); NFPA 70®, National Electrical Code®, Chapter 9, Table 9 (cable resistance and reactance used in the worked example).

Cite or share this tool

Dreiym Engineering. Per-unit fault current calculator. Method: per-unit impedances on a common base; I = 1 ÷ |Z| × MVA base ÷ (1.732 × kV). https://www.dreiym.com/per-unit-calculator/

Instructors and shops are welcome to link to this tool or put its address on a handout. It is free, needs no sign-up and works on a phone.

How to use the calculator

Choose the one-line or the base converter. For the one-line, keep 100 MVA as the system base, enter the utility voltage and its available fault level in MVA or kA with its X/R, then list up to six elements in order from the source to the fault: transformers from their nameplate (kVA, %Z, X/R and the two voltage ratings), cables from their ohms per length and the number of parallel sets, and reactors from their ohms and X/R. Pick the bus where the fault is and, if motors run at that bus, enter their total size. The result shows the fault current, the X/R at the fault and the fault MVA, and the full table lists every element in ohms and per unit so you can check it by hand.

How to calculate fault current with the per-unit method

  1. Pick a base. Choose one MVA base for the whole system, usually 100 MVA, and use the source voltage as the base voltage of the first zone.
  2. Set the base voltage of each zone. Every transformer starts a new zone. Its base voltage is the base of the zone before it times the transformer’s secondary rating divided by its primary rating.
  3. Put each element on the system base. Divide ohms by the zone base impedance, kV² ÷ MVA. Move a transformer’s %Z from its own kVA and voltage to the system base with Zpu new = Zpu old × (kV old ÷ kV new)² × (MVA new ÷ MVA old). Split each impedance into R and X with its X/R ratio.
  4. Add the series path. Add the R values and the X values of the source and every element between the source and the fault.
  5. Add the motors in parallel. Convert the motors’ subtransient reactance to the system base and combine it with the path: Z = Z1 × Z2 ÷ (Z1 + Z2).
  6. Find the current. With a prefault voltage of 1.0 per unit, the fault current is 1 ÷ |Z| per unit. Multiply by the base current at the fault bus, MVA ÷ (1.732 × kV), to get kA.

Formulas

  • Base impedance: Zbase = kV² ÷ MVA, in ohms.
  • Base current: Ibase = MVA ÷ (1.732 × kV), in kA.
  • Per unit from ohms: Zpu = Z ÷ Zbase. Per unit from percent: Zpu = %Z ÷ 100.
  • Change of base: Zpu new = Zpu old × (kV old ÷ kV new)² × (MVA new ÷ MVA old).
  • R and X from Z and X/R: R = Z ÷ √(1 + (X/R)²), X = R × X/R.
  • Utility source: Zpu = MVA base ÷ short-circuit MVA, with short-circuit MVA = 1.732 × kV × kA.
  • Fault current: I = Ibase ÷ |Z|. Fault MVA = MVA base ÷ |Z|. X/R at the fault = X ÷ R of the total impedance.

Worked example

A 13.8 kV utility service with 500 MVA available at an X/R of 15 feeds a 1,500 kVA transformer, 13.8 kV to 480 V, 5.75% impedance and X/R 6. The secondary runs 100 ft through four sets of 500 kcmil copper in steel conduit (0.029 + j0.048 Ω per 1,000 ft, from NEC Chapter 9, Table 9) to a switchboard with 500 hp of 460 V motors. Base: 100 MVA, 13.8 kV on the primary and 0.48 kV on the secondary, where Zbase is 0.002304 Ω and Ibase is 120.28 kA.

ElementWorkingR puX pu
Utility100 ÷ 500 = 0.2 pu, split at X/R 150.013300.1996
Transformer0.0575 × 100 ÷ 1.5 = 3.833 pu, split at X/R 60.63023.781
Cable(0.029 + j0.048) × 100 ÷ 1,000 ÷ 4 = 0.000725 + j0.0012 Ω, ÷ 0.0023040.31470.5208
Path to the switchboardSum of the three0.95824.502
Motors500 hp as 500 kVA, X”d 0.25 at X/R 6, × (0.46 ÷ 0.48)² × (100 ÷ 0.5)7.65345.92
At the faultPath in parallel with the motors0.85564.100

|Z| = √(0.8556² + 4.100²) = 4.189 pu. Fault current = 120.28 ÷ 4.189 = 28.72 kA symmetrical. X/R = 4.100 ÷ 0.8556 = 4.79. Fault level = 100 ÷ 4.189 = 23.9 MVA. The utility path gives 26.13 kA and the motors 2.58 kA.

Assumptions

  • The fault is a balanced three-phase fault, so only the positive-sequence network is used. Line-to-ground and line-to-line faults need the negative and zero sequence networks too.
  • The voltage before the fault is 1.0 per unit of the bus base voltage.
  • The fault is bolted: no arc resistance and no fault resistance.
  • Load current before the fault is ignored.
  • Motors are represented by their subtransient reactance only, so the result is the first-cycle symmetrical current. Their contribution decays over the next few cycles, which the calculator does not model.
  • The system is radial: one source and one series path to the fault, with motors only at the fault bus.
  • Results are symmetrical rms currents. The DC offset and the asymmetrical peak are not included.

Frequently asked questions

Why use per unit for fault calculations?

Per unit turns every impedance into a fraction of a base, so a transformer looks the same from either side and a whole system with several voltages becomes one simple circuit. Equipment impedances already come in percent of their own rating, which is per unit times 100, so most of the data needs only a change of base.

How do I change the base of an impedance?

Multiply the per-unit value by the square of the old base voltage over the new one, and by the new base MVA over the old one. A transformer of 1,500 kVA at 5.75% has 0.0575 × 100 ÷ 1.5 = 3.833 per unit on a 100 MVA base at its rated voltage.

Is a transformer’s %Z on its own base?

Yes. The nameplate %Z is on the transformer’s own kVA rating and rated voltages. The calculator converts it to the system base, and when a rated voltage differs from the zone base voltage it applies the (rated kV ÷ base kV)² correction and says so.

How does the calculator handle motor contribution?

Running motors act as small generators for a few cycles after a fault. The calculator takes the total motor load at the fault bus, one hp as about one kVA, with its subtransient reactance and X/R, converts it to the system base and places it in parallel with the source path. Because the currents are added with their angles, the total can differ slightly from the plain sum of the two contributions.

Does the choice of base MVA change the answer?

No. The per-unit impedances and the base current change together, so the fault current in kA is the same on any base. 100 MVA is common because it keeps utility and plant values in a familiar range.

Why can the result differ from the available fault current calculator?

The point-to-point result of the available fault current calculator adds impedance magnitudes, while this calculator adds R and X separately: the two agree when every element has the same X/R, and the per-unit result is slightly higher when the X/R values differ. The sequence network section on that page works in per unit like this one and also covers line-to-ground and line-to-line faults. Both of its methods can reduce the transformer %Z by a tolerance factor such as 0.9; to compare, enter the same reduced %Z here.

When to bring in an engineer

A radial sketch is a good check, but a real system has more sources, more branches and equipment ratings to verify. Dreiym’s licensed Professional Engineers build the full model in a short circuit study, check each device’s interrupting and withstand rating, and carry the results into arc flash and coordination work, PE-stamped where required. Related tools: the available fault current calculator and, to go from the fault current to incident energy, the arc flash calculator. See our short circuit analysis and electrical power studies services, or contact us for a free quote. We typically respond within one business day.