Ground Rod Resistance Calculator: One Rod, Two Rods, Concrete
Resistance to earth of one ground rod, two rods, rods in a line or a rod in concrete, with the published forms of Dwight's formula side by side.
Tool referenceDE-TOOL-10729
- Method
- Dwight 1936; MIL-HDBK-419A Eqs. 2-15 to 2-25
- Electrodes
- One rod, two rods, rods in a line, rod in concrete
- Output
- Resistance to earth, rod length for a target
This ground rod resistance calculator estimates the resistance to earth of one or more driven rods in uniform soil. In the worked example a 10 ft rod, 3/4 in in diameter, in 100 Ω·m soil comes to 32.1 Ω by Dwight’s formula, and a second rod one rod length away brings the pair to 18.2 Ω, not half of 32.1 Ω.
Ground rod and electrode resistance calculator
Resistance to earth of one driven ground rod, two rods, rods in a line or a rod set in concrete, in uniform soil. The result shows the published forms of the formula side by side, so you can see why free calculators give different numbers for the same rod. The answer updates as you type.
The calculator needs JavaScript®. The formulas and a worked example are on this page.
Quick start Fills in the form. Change anything after.
Result
32.1 Ω, above your 25 Ω target
One 10 ft rod in 100 Ω·m: 32.1 Ω by Dwight's formula.
To reach 25 Ω with this arrangement the rods would need to be about 13.5 ft long, in the same soil.
About 86% of one rod's resistance lies in the soil within 10 ft of the rod, and 92% within 20 ft (MIL-HDBK-419A Eq. 2-20).
- Resistance to earth
- 32.1 Ω
- One rod alone
- 32.1 Ω
- Within one rod length
- 86%
A calculation is not a measurement. Uniform soil, rods flush with the surface, no seasonal change. Real soil is layered and its resistivity changes with moisture and temperature; confirm with a fall-of-potential test. See ground testing, or ask an engineer.
The same single rod by each published form
| Form and source | Result | Against Dwight |
|---|---|---|
| Dwight 1936: ρ/(2πL) × (ln(4L/a) − 1), a = radius. Same as BS 7430 with ln(8L/d) − 1 | 32.1 Ω | |
| MIL-HDBK-419A Eq. 2-16, empirical: ρ/(2πL) × ln(3L/d) | 32.2 Ω | +0.3% |
| MIL-HDBK-419A Eq. 2-15: ρ/(2πL) × ln(4L/d) | 33.7 Ω | +5% |
| Dwight's form with the diameter written in place of the radius: ρ/(2πL) × (ln(4L/d) − 1) | 28.5 Ω | −11.3% |
Full results and steps
| Arrangement | one rod |
|---|---|
| Soil resistivity | 100 Ω·m |
| Rod length | 3.048 m |
| Rod diameter | 19.05 mm |
| One rod alone (Dwight) | 32.1 Ω |
| Resistance to earth | 32.1 Ω |
| Share within one rod length | 86% |
| Share within two rod lengths | 92% |
- In SI units: ρ = 100 Ω·m, L = 3.048 m, d = 0.01905 m (a = d/2).
- One rod (Dwight): ρ/(2πL) = 5.2216 Ω; ln(4L/a) = ln(8L/d) = 7.1546; R = 5.2216 × (7.1546 − 1) = 32.137 Ω.
- Share beyond one rod length (MIL-HDBK-419A Eq. 2-20): log(1 + √2) ÷ log(3L/d), with ln(3L/d) = 6.1738; inside: 86%.
Need the measured value?
Dreiym's licensed Professional Engineers measure soil resistivity and ground resistance with fall-of-potential and Wenner tests, and design grounding systems for layered soil.
Assumptions and limits
Assumptions: uniform soil of one resistivity; rods vertical with their tops flush with the surface; rods much longer than their diameter; the connecting conductor adds nothing; for concrete, a rod centred in a concrete cylinder as long as the rod.
What this does not check: layered soil, frozen or dry seasons, horizontal footing electrodes, grids, the code requirements that apply to your installation, or step and touch voltages.
Screening tool: Screening estimate for education and planning. Not an engineering study or a design, and not a substitute for a licensed engineer's review where one is required.
How the calculation works
- One rod: R = ρ/(2πL) × (ln(4L/a) − 1), Dwight (1936), with a the radius. BS 7430 writes the same thing as ln(8L/d) − 1.
- Two rods at spacing s: Dwight's two-rod formula, MIL-HDBK-419A Eq. 2-21.
- N rods in a straight line: R = ρ/(2πLN) × (ln(4L/a) − 1 + (2L/s) ln(2N/π)), MIL-HDBK-419A Eq. 2-25.
- Rod in concrete: R = (ρc ln(Dc/d) + ρ (ln(8L/Dc) − 1)) / (2πL), Fagan and Lee (1970) as given by Al-Shawesh et al. (2021), Eq. 45.
- Share of the resistance near the rod: MIL-HDBK-419A Eq. 2-20. Rod length for a target: found by halving the interval until the result matches.
Sources
Sources: MIL-HDBK-419A, Grounding, Bonding, and Shielding for Electronic Equipments and Facilities, Vol. I, Basic Theory (US Department of Defense, 1987), Eqs. 2-15, 2-16, 2-20, 2-21, 2-24, 2-25 and Table 2-2; Vol. II, Applications, 1.2.2.2; Y. Al-Shawesh, S.C. Lim and M. Nujaim, Analysis of the design calculations for electrical earthing systems, International Review of Electrical Engineering 16(2), 2021, Eqs. 6, 7 and 45 (open access); H.B. Dwight, Calculation of resistances to ground, Electrical Engineering 55, December 1936, pp. 1319 to 1328 (as cited in both).
Cite or share this tool
Dreiym Engineering. Ground rod resistance calculator. Method: Dwight (1936) and MIL-HDBK-419A, uniform soil. https://www.dreiym.com/ground-rod-resistance-calculator/
Instructors and shops are welcome to link to this tool or put its address on a handout. It is free, needs no sign-up and works on a phone.
Link copied.Citation copied.The copy did not work. The text is selected, so copy it with your device.AccessedHow to use the calculator
Choose the arrangement, enter the rod length and diameter and the soil resistivity, and add a target resistance if you have one. The result gives the resistance to earth, the rod length that would reach your target, how much of the resistance sits in the soil close to the rod, and the same rod worked out with each published form of the formula. The address keeps your inputs, so a copied link opens the same case.
How to estimate the resistance of a ground rod
- Measure the soil resistivity. A Wenner four-pin test gives the resistivity at the depth of the rods. Our Wenner workbench on the soil corrosivity page fits readings to two-layer soil.
- Choose the electrode. One rod, two rods, several rods in a line, or a rod set in concrete.
- Enter the rod size. The driven length and the outside diameter, and the spacing for more than one rod.
- Read the result. Compare the resistance with your target and look at the forms side by side to see how much the choice of formula matters.
- Measure the installed electrode. A fall-of-potential test gives the real value, which is what counts.
Worked example
- One rod 10 ft (3.048 m) long and 3/4 in (19.05 mm) in diameter, in 100 Ω·m (10,000 Ω·cm) soil: ρ/(2πL) = 100 ÷ (2π × 3.048) = 5.22 Ω; ln(8L/d) = ln(1,280) = 7.15; R = 5.22 × (7.15 − 1) = 32.1 Ω.
- MIL-HDBK-419A reads 32 Ω for the same rod and soil from its nomograph (Vol. II, 1.2.2.2).
- About 86 % of that resistance lies in the soil within 10 ft of the rod and 92 % within 20 ft (MIL-HDBK-419A Eq. 2-20).
- To reach 25 Ω with one rod in this soil, the rod would have to be about 13.5 ft long.
- A second rod 10 ft away gives 18.2 Ω for the pair, 57 % of one rod; at 20 ft, 17.3 Ω. Four rods in a line 20 ft apart give 9.25 Ω.
Why free calculators give different answers
The resistance of a driven rod has been written in several ways since Dwight published his formulas in 1936, and each form keeps or drops a different simplification. Dwight’s form uses the radius a: R = ρ/(2πL) × (ln(4L/a) − 1). BS 7430 writes the same thing with the diameter, ln(8L/d) − 1. MIL-HDBK-419A gives ln(4L/d), from a rod treated as a row of small spheres, and an empirical ln(3L/d) that it calls a better approximation, about 10 % lower. Since 8 divided by e is 2.94, Dwight’s form and the 3L/d form land close together.
| Form | Source | 10 ft × 3/4 in rod, 100 Ω·m |
|---|---|---|
| ρ/(2πL) × (ln(4L/a) − 1) | Dwight 1936; same as BS 7430 Eq. 6 | 32.1 Ω |
| ρ/(2πL) × ln(3L/d) | MIL-HDBK-419A Eq. 2-16 | 32.2 Ω |
| ρ/(2πL) × ln(4L/d) | MIL-HDBK-419A Eq. 2-15 | 33.7 Ω |
| ρ/(2πL) × (ln(4L/d) − 1) | Dwight’s form with the diameter in place of the radius | 28.5 Ω |
The last row is the common slip: writing Dwight’s ln(4L/a) − 1 with the diameter gives about 11 % less. We checked two free pages on 19 November 2026. One writes Dwight’s formula with the radius and gets 35 Ω for a rod 300 cm long and 1.27 cm in diameter in 10,000 Ω·cm soil; this calculator gives 34.7 Ω. The other writes the formula with the diameter, but its own worked example enters the radius (7.94 mm for a 5/8 in rod) and prints 59.8 Ω, which is Dwight’s value; following its written definition with the diameter gives 53.1 Ω.
Groups of rods add a second layer of differences. For two rods 10 ft apart, Dwight’s full two-rod formula (MIL-HDBK-419A Eq. 2-21) gives 18.2 Ω, while the simpler formula for rods in a line (Eq. 2-25) gives 17.3 Ω for the same two rods.
One rod or two?
MIL-HDBK-419A (1987) summarizes the National Electrical Code® of its time: a single rod, pipe or plate electrode that does not have a resistance to ground of 25 Ω or less is to be augmented by one additional electrode. It adds that this 25 Ω limit has tended to set the norm for grounding resistance, and it sets a design goal of 10 Ω for military communications facilities. The current wording is in Article 250 of the NEC® edition adopted where you work; this page does not quote it.
A second rod helps less than people expect. The same handbook says the spacing in a group of rods should be no less than one rod length and no more than two. In the worked example, a second rod one rod length away gives 57 % of one rod, not 50 %, because the two rods share the soil around them.
Why a measured value differs
Every formula here assumes one uniform soil. Real soil is layered, and MIL-HDBK-419A shows its resistivity changing with moisture, temperature and salt content, so the same rod reads differently through the year. The contact between the rod and the soil also matters: the handbook notes that granular earth such as gravel makes very poor contact. That is why the installed electrode is measured. Our article on fall of potential and point-to-point testing explains what each test proves, and how often ground systems should be tested covers the schedule.
Ufer (concrete-encased) electrodes
The concrete-encased electrode of the NEC®, often called a Ufer ground, is usually a bar or wire laid horizontally in a footing. We did not find a free published formula for that layout that we could check, so the calculator leaves it out. Our article on Ufer grounds covers how they are inspected and tested.
The concrete option in the calculator is a vertical rod centred in a concrete cylinder, by the formula of Fagan and Lee (1970) as given by Al-Shawesh, Lim and Nujaim (2021). They give 30 to 90 Ω·m as typical for concrete buried in soil. With 6 in of concrete at 30 Ω·m around the rod of the worked example, the result is 24.5 Ω, against 32.1 Ω for the bare rod.
Method and sources
- MIL-HDBK-419A, Grounding, Bonding, and Shielding for Electronic Equipments and Facilities, Vol. I, Basic Theory, and Vol. II, Applications (US Department of Defense, approved 29 December 1987; DTIC AD-A239 565 and AD-A239 808). Used: Eqs. 2-15, 2-16, 2-20, 2-21, 2-24 and 2-25, Table 2-2 (approximate soil resistivity, for the unit warning), 2.6.2 (rod spacing), Vol. II 1.2.2.2 (example). Approved for public release, distribution unlimited.
- Y. Al-Shawesh, S.C. Lim and M. Nujaim, Analysis of the design calculations for electrical earthing systems, International Review of Electrical Engineering 16(2), 2021, pp. 104 to 117. Used: Eqs. 6, 7, 12 and 45, and the typical concrete resistivity in II.8. Open access under CC BY-NC-ND 3.0; we use the formulas and values with this citation.
- H.B. Dwight, Calculation of resistances to ground, Electrical Engineering 55, December 1936, pp. 1319 to 1328, and E.J. Fagan and R.H. Lee, IEEE® Transactions on Industry and General Applications, 1970: cited through the two sources above, which we read.
- Method last checked against these sources on 19 November 2026.
Verified against
| Case | Published value | This calculator |
|---|---|---|
| 10 ft × 3/4 in rod, 10,000 Ω·cm | 32 Ω, MIL-HDBK-419A Vol. II, 1.2.2.2 (nomograph) | 32.1 Ω |
| 10 ft × 1 in rod, share beyond 10 ft and 20 ft | 0.15 and 0.08, MIL-HDBK-419A Vol. I, p. 2-20 | 0.15 and 0.08 |
| 100 ft × 1 in rod, share within 100 ft and 200 ft | 89 % and 94 %, same pages | 89 % and 94 % |
| Two rods at a spacing of one rod length | Eq. 2-24 constant −0.18 | Eq. 2-21 gives −0.174 |
| 300 cm × 1.27 cm rod, 10,000 Ω·cm | 35 Ω, eepower.com, How to improve resistance to ground | 34.7 Ω |
| 8 ft × 5/8 in rod, 150 Ω·m | 59.8 Ω, worked example on a free calculator page | 59.9 Ω |
| BS 7430 form against Dwight’s form | The same result, Al-Shawesh et al. 2021 | Equal to 9 digits |
These cases are part of the unit tests that run every time the calculator is built.
Frequently asked questions
What resistance should a ground rod have?
MIL-HDBK-419A (1987) summarizes the NEC® rule of its time: a single rod, pipe or plate electrode that is not 25 ohms or less to ground is to be augmented by one additional electrode. Other systems set lower goals; the same handbook uses 10 ohms for military communications facilities. Check the NEC® edition and any local rules that apply to your installation.
Does a second ground rod cut the resistance in half?
No. Two rods share the soil around them, so the pair gives more than half of one rod. In the worked example, a 10 ft rod in 100 ohm-m soil is 32.1 ohms alone and 18.2 ohms with a second rod 10 ft away, 57 percent of one rod.
Why do ground rod calculators give different answers for the same rod?
They use different published forms of the formula: Dwight with the radius, BS 7430 with the diameter, or the MIL-HDBK-419A forms with 4L/d or 3L/d. Writing Dwight’s formula with the diameter where it needs the radius gives about 11 percent less. The calculator shows all four forms side by side.
Should I enter soil resistivity in ohm-meters or ohm-centimeters?
Either: the calculator has a switch. One ohm-meter is 100 ohm-centimeters, so a mix-up changes the result a hundredfold. The calculator warns when the value is outside the 10 to 10,000 ohm-m span of soils in MIL-HDBK-419A Table 2-2.
Can a calculation replace a ground resistance test?
No. The formulas assume uniform soil and a rod in good contact with it. Layered soil, moisture, temperature and contact all change the real value, which a fall-of-potential test measures.
When to bring in an engineer
A calculation helps decide how many rods to plan for. When the electrode has to meet a requirement, protect equipment or carry fault current, it is measured and designed for the real soil. Dreiym’s licensed Professional Engineers handle ground testing and commissioning and soil resistivity surveys. See also how grounding electrodes are tested, or more engineering calculators.