How Much Current Is Dangerous? Shock Thresholds from OSHA, NIOSH and Dalziel

Places a body current, or a voltage and a body resistance, on the published tables of OSHA, NIOSH and Dalziel side by side.

Tool referenceDE-TOOL-10732

Sources
OSHA 3075, NIOSH 98-131, Dalziel 1961
Inputs
Current, or voltage and body resistance; duration
Output
Rows reached on each table, Dalziel line

How much current is dangerous depends on whose table you read, but the published figures agree on the shape: about 1 mA is felt, the let-go range starts around 6 to 9 mA, and NIOSH lists 100 mA of 60 Hz current through the chest as the ventricular fibrillation threshold. The same 120 V drives about 1 mA through dry skin and 120 mA through wet skin, which is why current, not voltage alone, decides the effect.

How much current is dangerous? Body current on three published tables

It is the current through the body, not the voltage alone, that sources use to describe the effect of a shock. Enter a current, or a voltage and a body resistance, and see where it falls on the tables of OSHA, NIOSH and Charles Dalziel, side by side. The tables do not agree exactly; the page below explains why.

The explainer needs JavaScript®. The three tables are on this page.

Quick start Fills in the form. Change anything after.

What you know
Start from

NIOSH 98-131 gives these three values. Real resistance depends on the contact area, the path through the body, moisture and the voltage itself; the values are examples, not a measurement of a person.

The shock
Current type

Dalziel's line covers 1/120 s to 5 s, 60 Hz AC.

Result

120 mA: at or above the 100 mA NIOSH lists as the ventricular fibrillation threshold

Ohm's law: 120 V ÷ 1,000 Ω (wet or broken skin, NIOSH) = 120 mA.

OSHA 3075 (hand to foot, 1 second): for men in the row "Extreme pain, respiratory arrest" (50 mA to 150 mA); for women in the row "Extreme pain, respiratory arrest" (50 mA to 150 mA).

NIOSH 98-131 (60 Hz through the chest): at or above "100 mA, ventricular fibrillation threshold".

Dalziel 1961, Table II (60 Hz AC): for men at or above "possible fibrillation, 3 s shocks"; for women at or above "possible fibrillation, 3 s shocks".

Dalziel (1961) drew the line below which fibrillation is unlikely at 165/√T mA, with T in seconds: 165 mA for 1 s. This current is below that line.

A GFCI shuts off the power when the current going out and coming back differ by more than 5 mA, within as little as 1/40 second (OSHA 3075). A common 15 or 20 A breaker opens at 15 or 20 A (NIOSH 98-131).

Body current
120 mA
Dalziel line at this duration, mA
165
Times the 5 mA GFCI level
24

An explainer, not medical advice or a safety design tool. These are published research and agency figures for adults; they do not cover children or medical implants. See forensic electrical engineering, or ask an engineer.

The current on the three tables120 mA placed on the OSHA, NIOSH and Dalziel tables.OSHANIOSHDalziel menDalziel women0.1 mA1101001 A10 AGFCI 5 mA
Log scale. Ticks: the rows of each table. Dashed: 5 mA GFCI level. Orange: your current.
Dalziel's fibrillation line against shock durationDalziel's line at 1 s is 165 mA; your current is 120 mA.0.010.1110101001 A10 A165/√T mAShock duration, s
Log scales. Dot: your current and duration.

The three tables, with the rows this current reaches

SourceCurrentWhat the source says
OSHA 3075 (2002), hand to foot, 1 sBelow 1 mAGenerally not perceptible
1 mAFaint tingle
5 mASlight shock felt; not painful but disturbing; average person can let go
6 to 25 mA (women); 9 to 30 mA (men)Painful shock, loss of muscular control; the freezing current or let-go range
50 to 150 mAExtreme pain, respiratory arrest, severe muscular contractions; death is possible
1,000 to 4,300 mARhythmic pumping action of the heart ceases; death likely
10,000 mACardiac arrest, severe burns; death probable
NIOSH 98-131 (1998), 60 Hz through the chest1 mABarely perceptible
16 mAMaximum current an average man can grasp and let go
20 mAParalysis of respiratory muscles
100 mAVentricular fibrillation threshold
2 ACardiac standstill and internal organ damage
15 or 20 ACommon fuse or breaker opens circuit
Dalziel (1961) Table II, mA, men / women, 60 Hz AC unless DC0.4 / 0.3; DC 1 / 0.6Slight sensation on hand
1.1 / 0.7; DC 5.2 / 3.5Perception threshold, median
1.8 / 1.2; DC 9 / 6Shock, not painful, muscular control not lost
9 / 6; DC 62 / 41Painful shock, muscular control lost by 1/2 %
16 / 10.5; DC 76 / 51Painful shock, let-go threshold, median
23 / 15; DC 90 / 60Painful and severe shock, breathing difficult, muscular control lost by 99 1/2 %
100 / 100; DC 500 / 500Possible ventricular fibrillation, three-second shocks
Full results and steps
Voltage120 V
Body resistance1,000 Ω
Body current120 mA
Current type60 Hz AC
Duration1 s
Dalziel line, 165/√T165 mA
  1. I = V ÷ R = 120 ÷ 1,000 = 120 mA.
  2. Dalziel: 165 ÷ √1 = 165 mA.
  3. 120 mA ÷ 5 mA (GFCI level) = 24.

Investigating an electrical shock?

Dreiym's licensed Professional Engineers investigate electrical incidents: the source of the voltage, the path, the protective devices and why they did or did not operate.

Assumptions and limits

What the numbers are: OSHA's table is for current from hand to foot for one second; NIOSH's is for 60 Hz current through the chest; Dalziel's are from tests on volunteers (perception and let-go) and from animal data scaled to people (fibrillation). Thresholds vary from person to person, which is why Dalziel gives medians and 1/2 % and 99 1/2 % values.

What this does not cover: children, medical implants, frequencies other than 60 Hz, burns, injuries from falls, and the design of protective systems.

Not medical advice: An explainer of published figures for education. Not a medical assessment and not a design tool for protective systems.

How the calculation works
  • From a voltage: I = V ÷ R, Ohm's law, with a body resistance from NIOSH 98-131 or your own value.
  • Each table row is a current at which the source describes an effect; the tool marks the last row the current reaches.
  • OSHA lists separate let-go ranges for women (6 to 25 mA) and men (9 to 30 mA).
  • Dalziel's fibrillation line: I = 165 ÷ √T mA, T in seconds, for 60 Hz shocks from 1/2 cycle to 5 seconds (Dalziel 1961, Eq. 3).
Sources

Sources: OSHA 3075, Controlling Electrical Hazards (US Department of Labor, 2002, revised), pages 7 and 13; NIOSH 98-131, Worker Deaths by Electrocution (May 1998), pages 6 and 7, Table 1; C.F. Dalziel, Deleterious Effects of Electric Shock, ILO Meeting of Experts on Electrical Accidents and Related Matters, Geneva, 1961 (E.A.R.M./1961/D.2), Table II and Eq. 3.

Cite or share this tool

Dreiym Engineering. How much current is dangerous?. Sources: OSHA 3075 (2002), NIOSH 98-131 (1998), Dalziel (1961). https://www.dreiym.com/how-much-current-is-dangerous/

Instructors and shops are welcome to link to this tool or put its address on a handout. It is free, needs no sign-up and works on a phone.

How to use the explainer

Start from a current, or from a voltage and one of the body resistances NIOSH gives, then choose AC or DC and the duration. The result places the current on the tables of OSHA, NIOSH and Dalziel side by side, marks the 5 mA level at which a GFCI trips, and, for 60 Hz shocks from 1/120 s to 5 s, compares it with Dalziel’s fibrillation line.

How to work out the current through the body

  1. Find the voltage. The voltage between the two points the body touched, for example an energized part and the ground.
  2. Pick a body resistance. NIOSH gives up to 100,000 Ω for dry skin, 1,000 Ω for wet or broken skin and 500 Ω once high voltage has broken the skin down.
  3. Apply Ohm’s law. Current = voltage ÷ resistance.
  4. Compare with the tables. Read the current against the OSHA, NIOSH and Dalziel tables, noting the path and duration each one assumes.
  5. Allow for the duration. For short 60 Hz shocks, Dalziel’s line 165/√T mA shows how the fibrillation level falls as the shock gets longer.

Current, not voltage

OSHA lists four things that set the severity of a shock: the amount of current through the body, its path, how long the body stays in the circuit, and the frequency. Voltage matters because it drives the current through the body’s resistance. NIOSH works the numbers: at 120 V, dry skin at 100,000 Ω lets about 1 mA through, a barely perceptible current, and wet skin at 1,000 Ω lets 120 mA through. At 1,000 V, skin broken down to 500 Ω carries 2 A.

Why the published thresholds disagree

SourceLet-go currentConditions
OSHA 3075 (2002)6 to 25 mA (women), 9 to 30 mA (men)60 Hz, hand to foot, 1 second; OSHA cites Kouwenhoven (1968)
NIOSH 98-131 (1998)16 mA, the most an average man can grasp and let go60 Hz
Dalziel (1961), Table IIMedian 16 mA (men), 10.5 mA (women); 1/2 % lose control at 9 and 6 mA; 99 1/2 % at 23 and 15 mA60 Hz, tests on volunteers; DC median 76 mA (men)
The Physics Factbook (2000), a student essay5 to 7 mA (women), 7 to 9 mA (men)No conditions stated

The numbers differ for reasons that can be traced. Dalziel measured a spread of values across people and reported the median and the 1/2 and 99 1/2 percent points; one page quotes the median, another the lowest values. The current path differs (hand to foot for OSHA, through the chest for NIOSH), as do the duration and the kind of current: Dalziel’s let-go current for direct current is several times the 60 Hz value. Pages that quote other pages often drop these conditions, and The Physics Factbook gathers quoted fatal currents from 0.06 A to 0.3 A from textbooks and class notes.

What a GFCI does, and why a breaker does not protect people

OSHA explains that fuses and circuit breakers are designed to protect conductors and equipment, opening when too much current flows. A ground-fault circuit interrupter compares the current going out to the equipment with the current coming back and shuts off the power when the difference exceeds 5 mA, within as little as 1/40 of a second. NIOSH puts the scale in view: contact with 20 mA can be fatal, while a common household breaker is rated 15, 20 or 30 A. Our article on ground faults and short circuits explains the difference.

Water and wet skin

OSHA notes that dry skin has a fairly high resistance but moist or wet skin acts as a conductor, and NIOSH adds that standing water, wet clothing, high humidity and perspiration increase the possibility of a low-voltage electrocution. Wet skin takes the body from up to 100,000 Ω to about 1,000 Ω, a hundredfold more current at the same voltage. See how electricity conducts through liquids and what NEC® Article 680 requires for pool bonding.

For engineers: Dalziel’s fibrillation line

In his 1961 paper for the International Labour Office, Dalziel analysed fibrillation tests on animals, scaled to a 70 kg person, and found the lowest values bounded by a line of slope −1/2: I = K/√T, with I in milliamperes and T in seconds, and K from 165 to 185 at the 1/2 percent level. Table II of the paper uses 165/√T. He limits the relation to shocks from 1/2 cycle to 5 seconds and writes that it is meant for engineering problems, not to explain the physiology. Later work, such as Dalziel and Lee’s 1968 re-evaluation of lethal currents cited by NIOSH, revised these constants; we could not read it free, so the explainer uses the 1961 equation.

Questions for the classroom

  1. Using NIOSH’s body resistances, what current flows at 120 V through dry skin, and through wet skin?
  2. Why does OSHA give one let-go range for women and another for men?
  3. A GFCI trips at a difference of 5 mA. Where does 5 mA fall on each of the three tables?
  4. By Dalziel’s line, how does the fibrillation level change when a shock lasts four times as long?

Method and sources

  • OSHA 3075, Controlling Electrical Hazards (US Department of Labor, 2002, revised), page 7, Effects of Electric Current in the Human Body (OSHA cites W.B. Kouwenhoven, Human Safety and Electric Shock, 1968), and page 13 on circuit protection devices. In the public domain.
  • NIOSH 98-131, Worker Deaths by Electrocution (May 1998), pages 6 and 7 and Table 1. A US Government work.
  • C.F. Dalziel, Deleterious Effects of Electric Shock, International Labour Office, Meeting of Experts on Electrical Accidents and Related Matters, Geneva, 23 to 31 October 1961 (E.A.R.M./1961/D.2), Table II and Eqs. 2 and 3. We reproduce the table values as data with this citation.
  • G. Elert (ed.), The Physics Factbook, Electric Current Needed to Kill a Human (Jack Hsu, 2000), for the comparison only.
  • Left out for lack of a free source: the time-current zones of IEC 60479-1 and the body-current constants of later standards such as IEEE® Std 80. Method last checked against these sources on 19 November 2026.

Verified against

CasePublished valueThis explainer
120 V, dry skin, 100,000 Ω1 mA, NIOSH 98-131 p. 71.2 mA
120 V, wet skin, 1,000 Ω120 mA, same page120 mA
1,000 V, 500 Ω2 A, same page2 A
Fibrillation line at 3 s95 mA, Dalziel 1961 p. 1495 mA
Fibrillation line at 1 s165/√1 = 165 mA, Dalziel Table II165 mA
GFCI trip levelMore than 5 mA, OSHA 3075 p. 135 mA not above, 5.1 mA above

These cases are part of the unit tests that run every time the explainer is built.

Frequently asked questions

How many milliamps can be fatal?

NIOSH lists 100 mA of 60 Hz current through the chest as the ventricular fibrillation threshold and notes that contact with 20 mA can be fatal. OSHA’s table, for current from hand to foot for one second, says death is possible from 50 to 150 mA. The figures depend on the path, the duration and the person.

Is it the voltage or the current that is dangerous?

The sources describe the effects by the current through the body. Voltage drives that current through the body’s resistance, so the same voltage can give about 1 mA through dry skin or 120 mA through wet skin, as NIOSH shows for 120 V.

What is the let-go current?

The largest current at which a person can still release a gripped conductor. Dalziel measured a median of 16 mA for men and 10.5 mA for women at 60 Hz; OSHA gives ranges of 9 to 30 mA for men and 6 to 25 mA for women.

Is direct current less dangerous than alternating current?

Dalziel’s Table II lists higher currents for direct current at every level: a median let-go of 76 mA for men against 16 mA at 60 Hz, and 500 mA against 100 mA for possible fibrillation in three-second shocks. That is a comparison of thresholds, not a statement that direct current is safe.

Does a circuit breaker protect people from shock?

OSHA explains that fuses and circuit breakers protect conductors and equipment. A common breaker is rated 15, 20 or 30 A, far above the currents in the shock tables. A GFCI shuts off the power when more than 5 mA leaks out of the circuit.

After an electrical injury

An injury is reconstructed from the scene and the equipment: the source of the voltage, the path, the protective devices and why they did or did not operate. Dreiym’s licensed Professional Engineers provide forensic electrical engineering. See also the consequences of an on-site electrocution injury, or explore circuits in the circuit simulator.

Need more than a screening estimate?

We typically respond within one business day.

Request a free quoteor call (866) 621-6920